Abstract

This paper introduces a new approach, based on faster-than-real-time (FTRT) analysis, to predict out-of-step (OOS) condition of a turbine-generator (T-G) unit subsequent to a fault scenario. The proposed FTRT analysis is based on 1) solving a state-space model of the T-G electromechanical system and corresponding controllers without the need for online measurements, and 2) an estimated Thevenin equivalent of the rest of the power system. The measurement-free FTRT analysis is carried out after the Thevenin parameters are estimated subsequent to the fault clearance instant. Equal area criterion is applied on the predicated variables to detect OOS condition. A reliable decision can be made based on this approach, since it does not involve simplifying assumptions contrary to the existing approaches. The FTRT approach accurately considers the impacts of the detailed model of the generator, automatic voltage regulator, prime mover, governor system, and the host power system. This paper provides detailed mathematical formulation for the proposed OOS detection method and verifies its feasibility and accuracy based on single machine and large test systems. The proposed approach is also implemented on an industrial platform and evaluated. The results confirm that the proposed approach can accurately identify OOS conditions, earlier than the rotor angle noticeably increases.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.