Abstract

This paper presents a frequency scanning analysis for detecting the potential of subsynchronous resonance (SSR) in induction generator based wind farms. Two types of induction generator: single-cage and double-cage based wind farms are considered. The wind farms are connected to modified IEEE First Benchmark and IEEE Second Benchmark System. Detailed positive sequence model of the study systems are developed and frequency scanning is carried out by calculating effective impedance looking from the rotor circuit of the induction generators. It is found that induction generator based wind farms are quite susceptible to SSR due to induction generator effect when they are connected to IEEE First Benchmark System. In this case, SSR may occur at realistic levels of series compensation if the wind farms employ double-cage induction generators. Incidentally, no SSR phenomenon is found in wind farms which are connected to IEEE Second Benchmark System. The frequency scanning results are compared and validated with eigenvalue analysis. Hence, frequency scanning technique can be successfully utilized for initial investigation of any potential for SSR in wind farms connected to a series compensated transmission line.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.