Abstract

Frequency Domain Spectroscopy (FDS) measurement is a popular technique for assessment of insulation condition. In the method a sinusoidal voltage of variable frequency is applied on the insulation system of electrical equipment like power transformer and the phase of corresponding current response is measured at each frequency. Present work investigates use of Triangular waveform of different frequency instead of sinusoidal to assess the insulation condition. Simulation study on digital model of oil paper condenser and experimental analysis on scaled down model of a transformer insulation shows that, triangular waveform of coarse frequency interval can be used instead of using sinusoidal waveform of finer frequency interval. Thus, it can reduce the cost of the FDS measurement system in a greater way, as generation of triangular waveform is easier than pure sinusoidal waveform.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.