Abstract

Over the past few years, frequency domain spectroscopy (FDS) has been widely utilized to assess transformer insulation. Many investigations have revealed that the FDS measurement has been observed to be dependent on service conditions (aging, moisture, geometry, and temperature). During the onsite FDS measurement, the inner insulation temperature of the de-energized transformer gradually decreases, which affects the FDS results due to moisture migration from oil to the cellulose insulation. This process gives rise to misinterpreting of the condition of the transformer insulation. Presently, the master curve technique reported by several researchers is utilized for temperature correction in FDS measurements. In fact, various researchers have obtained different master curves, so making a universal approach to temperature correction has become an important topic. In the present investigations, a series of experiments was performed on oil-impregnated pressboard insulation under laboratory conditions which was followed by FDS measurements at lower than operating temperature and a universal master curve for temperature correction was studied. Activation energies from oil-impregnated pressboard tests support the effectiveness of the proposed universal approach for temperature correction.