Abstract

In order to establish a method for monitoring contamination in insulators based on leakage current waveforms and their frequency characteristics, the leakage current waveforms and frequency characteristics of an artificially polluted 180 mm diameter cap and pin type insulator were investigated by the wet contaminant and the clean fog methods at fixed applied voltages. As a result it was found that leakage current waveforms become similar to the symmetrical wave when strong local arcs occur; hence, the intensity of the odd order of harmonic components, e.g. 50, 150, and 250 Hz, is high. Furthermore, it was clarified that the transition of the leakage current waveforms, until flashover occurs, is classified into six stages and that a threshold exists by which the occurrence of flashover can be predicted.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.