In order to know about the change features of leakage current during the pollution flashover process of composite insulators, the study of the pollution flashover test on composite insulator under the pollutional condition is presented in the artificial fog cabinet. The characteristics of leakage current waveforms in time-domain and frequency-domain are measured and analyzed during the test. The analysis results show that there is a strong correlation among the fundamental harmonic, the third harmonic and fifth harmonic. The characteristics of leakage current spectrum are represented by the maximum value of leakage current (Im), total harmonic distortion (THD), and phase difference of fundamental leakage current (θ). During a near-flash event, the leakage current exhibits high amplitude, low harmonic content, and small phase difference between the fundamental leakage current and voltage. The research findings provide a basis for establishing a pollution flash warning system based on leakage current characteristic quantities.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.