Abstract

The leakage detection of a water distribution system (WDS) needs the support of a large number of field data. This paper collected over 6800 leak detection signals from cast iron pipelines used in a WDS. We found that 3280 signals indicated leakage, and the remaining indicated no leakage. The characteristics of the signals were extracted and analyzed from three perspectives: the central frequency of the power spectrum, the spectral roll-off rate, and the spectral flatness. Significant statistical distributions were found. The central frequencies of the leakage signals followed the normal distribution, and their spectral roll-off rates demonstrated the Burr distribution; the Birnbaum–Saunders distribution could describe the spectral flatness of the signals. Based on these characteristics, the recognition rate of the ML model for leak detection was improved. The Random Forest model was used to classify the leakage detection signals. The recall rate was 100%, and the false positive rate was 8.27%.