Abstract

Through a macro inspection, chemical composition analysis, hardness inspection, graphite carbon inspection and energy spectrum analysis, the reason for the break of the energy storage spring of the circuit breaker in a 110kV substation are analyzed. The results show that poor manufacturing technology and anti-corrosion technology of the spring are the main reason for its fracture. Corresponding control measures are put forward to avoid similar failures from happening again.