Abstract
This paper presents an experimental study of upward and downward flow of boiling heat transfer characteristics for refrigerant 22 in and downstream of U-bends situated in a vertical plane. Three tubular test sections with 40 mm, 58 mm and 96 mm bend radius respectively have been used. They had an inner tube diameter of 16 mm, and outside diameter of 20 mm. The ranges of heat flux and mass velocity covered in the tests were 5–30 kW m −2 and 120 –420 kg m t-2s −1. Heat transfer coefficients show a strong variation with axial and radial position. The average heat transfer coefficients are higher both in the bends and also downstream of the bends compared with flow in an equivalent horizontal straight tube. Correlations are proposed to predict the average flow of boiling heat transfer coefficients of refrigerant flowing in U-bends.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.