Abstract

Energy Storage System (ESS) is a facility that can store electricity and supply power when needed, and is a very necessary element for new and renewable energy generation. Thermal runaway fires can occur due to various causes in ESS. These fires can cause different damage depending on the building structure and other building disaster prevention facilities. Therefore, it is necessary to evaluate the fire risk by deriving the frequency of occurrence of the cause of fire in the ESS and checking the severity factor that determines the damage scale. In this study, fire risk assessment of ESS was performed using risk matrix method. The risk assessment was conducted based on data collected based on fire cases and field investigations. Through risk assessment, it was confirmed that the main causes of ESS fires were EMS/BMS errors and battery abnormalities. In addition, as the structure of the ESS building is fire-resistant, the fire compartment is set, and the separation distance between battery facilities is larger, the damage caused by a fire is smaller.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.