Abstract
Telephone company customers reported audible noise in their telephone service. Through measurements, analysis, and simulations, 540 Hz noise was found to be coupling from power distribution to telephone cables in a shared underground right-of-way. The source of the noise was small single-phase electronic loads dispersed throughout the power distribution system in the area. A passive shunt filter was designed using an existing capacitor bank. Installation of this filter reduced the noise to acceptable levels.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.