Abstract

Harmonics generated by power converters have become a serious problem for the AC mains as they can only be removed by using bulky passive filters. Besides, harmonic compensation by shunt passive filters may cause undesirable interference such as resonance with the AC mains. To solve this problem, the authors propose a combined system of a shunt passive and series active filters. This system is self-adaptable and only a small power active filter is needed. The choice of the control algorithm, together with the AC mains and nonlinear load parameters determine its performance in static operation as well as in dynamic mode resulting from fluctuating loads. In this paper, the calculation of harmonic current references is considered first. Secondly the compensation characteristics of the whole filter are studied in steady state mode and some simulation results are presented. Finally the dynamic of the harmonic compensation is studied when the nonlinear load varies, so as to the appreciate the series active filter effect on harmonic compensation.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.