Abstract

Dam tunnel ventilation has been widely used in underground hydropower station to save energy. In order to study the dam tunnel cooling (heating) effect, a 24 hours continuous field measurement is conducted in underground multi-tunnels; and heat transfer performance about the dam tunnel has been calculated and analyzed. Meanwhile, to figure out influencing factors to dam tunnel ventilation and heat transfer performance, based on similarity theory, a small-scale experimental set-up is made to simulate heat transfer process during air passing through the tunnel. The experimental results show that the velocity and temperature of the inlet air both have significant impacts on heat exchange. Taking the underground dam tunnel as a huge natural “air conditioner” to replace some mechanical heat/cold sources is an energy-saving method for Heating, Ventilation and Air Conditioning system in hydroelectric power plants.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.