Abstract

Doubly fed induction generator (DFIG) based wind farms are being increasingly integrated into power grids with transmission lines, and distance protection is usually used as either the main or the backup protection for the transmission line. This paper analyzes the composition of a DFIG short circuit current and indicates the existence of a rotor speed frequency component. By analyzing several real fault cases of the DFIG-based wind farms connected to transmission lines, the weak power supply system and current frequency deviation of the wind farm side are illustrated. When a fault occurs on the transmission line, the short circuit current on the wind farm side is small and its frequency may no longer be nominal due to the existence of rotor speed frequency component, whereas the voltage frequency remains nominal frequency because of the grid support. As a result, the conventional distance protection cannot accurately measure the impedance, which can result in unnecessary circuit breaker tripping. Therefore, a time-domain distance protection method combined with the least-squares algorithm is proposed to address the problem. The efficacy of the proposed method is validated with real fault cases and simulation.

Highlights

  • In addressing the problems of environmental pollution and energy shortages, the world has been focusing on the development and use of wind energy, and large-scale wind farms are being increasingly integrated into the power grid

  • The proposed method can overcome the influence of frequency variation as a result that fault distances can be identified accurately and quickly when faults occur on the transmission line connected to a doubly fed induction generator (DFIG)-based wind farm

  • The time-domain distance protection method can accurately and quickly identify fault distances when faults occur on the transmission line connected to a DFIG-based wind farm

Read more

Summary

Introduction

In addressing the problems of environmental pollution and energy shortages, the world has been focusing on the development and use of wind energy, and large-scale wind farms are being increasingly integrated into the power grid. Fault characteristics of DFIG-based wind farms and the performance of distance protection when unbalanced faults occur on high voltage transmission lines should be further studied. The fault characteristics and distance protection applicability of the transmission lines connected to DFIG-based wind farms are obtained. The proposed method can overcome the influence of frequency variation as a result that fault distances can be identified accurately and quickly when faults occur on the transmission line connected to a DFIG-based wind farm.

Fault Analysis of DFIG-Based Wind Farm and Its Verification
DFIG Short Circuit Current
Fault Analysis of the DFIG-Based Wind Farm without LVRT Capability
Fault Analysis of the DFIG-Based Wind Farm with LVRT Capability
The Single-Phase Ground Fault Case
The Phase-to-Phase Short Circuit Fault Case
Application of Conventional Distance Protection
Phase-to-Ground Fault
Phase-to-Phase Fault
Time-Domain Distance Protection Based on the R-L Model
Case Studies
Findings
Conclusions