Abstract
This paper investigates the fault ride-through (FRT) capability of a hybrid AC/DC microgrid during both AC and DC network faults. In this investigation, commonly proposed FRT strategies for the distributed energy resources and AC and DC microgrids are implemented while the interlinking bidirectional converter is operated in power transfer mode. The investigations have shown that improvement in the AC network voltage is minimal during both AC and DC network faults. However, the DC network voltage improves and rapidly recovers after both AC and DC network faults. This is because while the AC network is relatively weak during the fault, the interlinking bi-directional converter tracks the pre-fault power reference following the fault clearance and assists with restoration of the DC bus voltage. However, this response could be detrimental if the hybrid AC/DC microgrid is operated in an islanded mode. Hence it is important to design a robust fault ride-through support scheme for the interlinking bi-directional converter in a hybrid AC/DC microgrid.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.