Abstract

This paper uses a scaled down version of the mixed cells modular multilevel converter (MMC) to discuss its modulation and capacitor voltage balancing method, and investigates its AC and DC fault ride-through capability. It has been found that the mixed MMC is resilient to both AC and DC network faults, which are necessary for next generations of highly meshed multi-terminal HVDC grids. The power losses comparison conducted in this paper has shown that the mixed cells MMC and three-level cells MMC achieve DC fault reverse blocking capability at reduced on-state losses than full-bridge MMC and alternative arm MMC.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.