Abstract

In China, the 10kV distribution network operates with neutral ungrounded. Due to the influence of high transition impedance and branches, the problem of fault location has not been effectively solved. The characteristics of C-type travelling wave method at neutral ungrounded system are analyzed in this paper. Multi-point fault location method based on C-type travelling wave method is proposed. By actively injecting high-voltage pulses into the circuit and using multiple measuring devices to detect the reflected wave of the fault point, the effect of high-impedance- grounded and branch points on the reflected wave of the fault point is effectively reduced, and the success rates of reflected wave detection of the fault point are improved. The validity of the method is verified by simulation.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.