Abstract
At present, the metal sheath of high voltage (HV) cables generally adopts the cross-bonded grounding method, which brings many types of faults and challenges the monitoring and diagnosis of the operation status of the cables. In order to effectively diagnose various types of faults in the metal sheath grounding system of HV cables, this paper proposes a fault diagnosis method for the metal sheath grounding system of HV cables based on long and short-term memory (LSTM). Firstly, the grounding system model of HV cable metal sheath is established. Secondly, the sheath currents of four faults are analyzed. Based on the sheath current amplitude ratio and phase difference of the same loop and the same grounding box, 14 feature vectors reflecting the operation state of the metal sheath grounding system are constructed. Then, the operation state of 18 kinds of metal sheath grounding systems is simulated, and the fault database is established. Finally, the LSTM algorithm is used to accurately identify the fault of HV cable grounding system. The results show that the LSTM algorithm can effectively diagnose and identify the faults of the HV cable metal sheath grounding system, and the accuracy rate is 100%.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.