Abstract
The motor driving end vibrates when there is no-load test run after overhaul of condensate pump of power plant unit; Through fault diagnosis and analysis, reasons for vibration were checked and solution found. The main reason is that the condensate pump motor magnetic force center line is not centered. The condensate pump motor is disassembled, then the reason of magnetic forcce center line is not centered was found and solution. Potential equipment safety hazard was eliminated successfully.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
More From: IOP Conference Series: Earth and Environmental Science
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.