Abstract

A fast and effective method for detecting and isolating faults in medium-voltage dc microgrids relies on rapid coordination between power supply converters and bus segmentizing contactors to limit currents and isolate faults without any need for fast communication between these active elements. The power converters independently enter current-limiting mode as soon as they recognize a fault condition and the segmentizing contactors autonomously decide whether or not to open based on their local interpretation of time-to-trip curves as functions of apparent circuit resistance. This method allows converters and contactors to use only local measurements when discerning whether or not to trip in order to isolate the faulted section. Simulation and experimental results show that low-impedance short-circuit faults can be isolated within 10–20 ms and the system can be reenergized within 40–60 ms. The method is effective for a wide range of fault and system configurations, and that range can likely be expanded by applying additional discrimination methods.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.