In this paper, improved principal component analysis (PCA) with joint angle analysis (JAA) is presented to detect and diagnose both fixed and drifting biases of sensors in variable air volume (VAV) systems. Fault characteristic concerned in PID controller in the VAV systems is analyzed and discussed. The squared prediction error (SPE) plot based on PCA is used to detect the sensor fixed and drifting biases. Then the JAA plot instead of conventional contribution plot is used to diagnose the faults. And they are tested and evaluated online in a simulated centralized VAV air-conditioning systems.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.