Abstract

This paper presents a comprehensive analysis of the harmonic sources of the single-phase grid-connected voltage source converter (VSC), which leads to an alternative approach for DC bus voltage control of the VSC under grid voltage distortion with a significant switching dead time. A selective current harmonic controller with the zero-reference structure plays a vital role in rejecting the harmonic components in the grid reference current created by the bus voltage control loop and the harmonic components in the grid voltage and in the VSC caused by the switching dead time. Therefore, the bus voltage control can adopt a conventional proportional-integral regulator tuned at a fast bandwidth. The proposed control scheme implemented in the multiple unbalanced synchronous reference frames was validated with a bidirectional 2-kVA VSC under grid voltage distortion and a significant dead time. Furthermore, the proposed control scheme exhibited the transient response and grid current quality superior to the conventional bus voltage control methods with a notch filter and a low-pass filter. The proposed control scheme has inherent frequency adaption.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.