Abstract

In this paper, the impact of direct liquid cooling (DLC) system failure on the IT equipment is studied experimentally. The main factors that are anticipated to affect the IT equipment response during failure are the CPU utilization, coolant set point temperature (SPT) and the server type. These factors are varied experimentally and the IT equipment response is studied in terms of chip temperature and power, CPU utilization and total server power. It was found that failure of the cooling system is hazardous and can lead to data center shutdown in less than a minute. Additionally, the CPU frequency throttling mechanism was found to be vital to understand the change in chip temperature, power, and utilization. Other mechanisms associated with high temperatures were also observed such as the leakage power and the fans speed change. Finally, possible remedies are proposed to reduce the probability and the consequences of the cooling system failure.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.