Abstract
When Bipole 1 was placed in service in the 1970s at +450 kVdc, bushings were found to be vulnerable to external flashovers. Bipole 2 at +500 kVdc in the 1980s had bushings with increased strike distance of 1 m and creepage increased from 32.9 mm/kV to 43.6 mm/kV. This made the Bipole 2 bushings vulnerable to radial puncture under non-uniform wetting. Booster sheds were installed to greatly reduce external flashovers of porcelain bushings in both HVDC bipoles. Recently the porcelain clad, oil filled wall bushings of Bipole 1 have been replaced with oil-free composite wall bushings having silicone rubber sheds.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
More From: IEEE Transactions on Dielectrics and Electrical Insulation
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.