Abstract

The insulation mechanism of UHVDC wall bushing is discussed. Design solution of the insulation structure is determined. In the solution, internal insulation includes SF6 gas-insulated and shielding structure, and external insulation is a type of composite insulating material, which is made up of epoxy FRP pipe and silicone rubber sheds. Creepage distance of external insulation and two types of shielding structures are designed in the paper. Finally two types of shielding structure are compared and optimized based on electric field simulation, and the result shows that dual-plate grounded shielding can enable the electric field strength of UHVDC wall bushing more evenly distributed.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.