Abstract

This paper presents an extended integral control to load frequency control (LFC) scheme with the presence of generation rate constraints (GRC) in order to get rid of overshoot of the conventional proportional-integral (PI) control. The conventional LFC scheme does not yield adequate control performance with the consideration of the singularities of speed-governor such as rate limits on valve position and GRC. In order to overcome this drawback, an extended integral control is developed for the PI control of the speed governor in the presence of GRC. The key idea of the extended integral control is using a decaying factor to reduce the effects of the error in the past. The decaying factor greatly affects the control performance, and should be carefully selected. This study determines the decaying factor in proportion to the degree of deviation in several levels. The computer simulation has been conducted for the single machine system with various load changes. The simulation results show that the proposed controller based on extended integral control yields much improved control performance, compared to the conventional PI controller.