Abstract

In this research work, the design of pipe in pipe, shell-and-tube and combined heat exchanger (previously mentioned types were combined to consider as one unit) has been made. These three heat exchangers have been utilized for two kinds of flows i.e., parallel as well counter flow types individually. The design of combined heat exchanger takes been proposed with the idea of increasing the heat transfer area and to understand the behavior of various parameters involved by comparing with the individual heat exchangers. 75:25 aqueous Ethylene Glycols, have been used as the working fluid in all three heat exchangers of counter as well parallel flow conditions. Total quantity of working fluid is 12 liters, in which 6liters of fluid is used as cold fluid and the other half is used as hot fluid. As a result, overall heat transfer coefficient (U) has been increased with increase of mass flow rate. Highest overall heat transfer coefficient value observed as 1943w/m2-k at highest mass flow rate (within the considerations of this work) of 0.145 kg/s. The highest decrement in LMTD recorded for 0.0425 to 0.145 increase of mass flow rate is 49.32% in shell-and-tube heat exchanger of parallel flow arrangement. The highest effectiveness is observed for pipe in pipe counter flow heat exchanger case, which is 0.39 at a mass flow rate of 0.145kg/s.