Abstract

DC system protection is more challenging than that for AC system due to the rapid rate of rise of the fault current and absence of natural current zero-crossing in DC systems. Superconducting fault current limiter (SFCL) in DC systems is a promising technology to reduce the fault current level and the rate of rise of the fault current, and also SFCLs have no resistance during normal operation. In this paper, the behaviors of an SFCL coil are investigated under both low impedance and high impedance fault conditions in DC systems. In the low impedance fault condition system, the SFCL coil performs effective limitation of the fault current level under different prospective fault current levels. The application of SFCLs with limited inductance in the DC system can be a potential solution to effectively suppress the fault current under low impedance short-circuit faults. The SFCL coil under the high impedance fault condition can only limit the prospective fault current when it is much higher than the critical current of the coil.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.