Abstract
The compressor speed, expansion valve opening and drying temperature are critical to the thermal performance improvement and control logic optimization of the closed heat pump drying (CHPD) system. This paper investigates the effects of the three parameters on the thermal performance of the CHPD system by the single factor experiment method. According to the experimental findings, as the compressor speed of the system increased, the heating capacity grew by 11.4%, but the coefficient of performance (COP) declined by 41.3%. As the expansion valve opening of the system increased, the heating capacity and COP grew by 73.5% and 82.9%, respectively. As the drying temperature of the system rose, the heating capacity grew by 3.1%, but the COP dropped by 25.3%. It can be concluded that reducing the compressor speed and drying temperature, and increasing the expansion valve opening could effectively enhance the thermal performance of the CHPD system.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.