Abstract

AbstractFoam extinguishing agents are crucial for the suppression of flammable liquid fires. Their thermal stability performance and heat insulation characteristics are critical indicators to evaluate the efficiency of the fire‐fighting foam. There have been some studies focused on exploring the behavior of fire‐fighting foams exposed to radiant heating. However, the decay mechanisms and heat transfer behaviors of the foam at the micro‐scale are still unclear and require further clarification. Therefore, in this study, the volume reduction coefficient, falling time of foam column height, and the temperature profiles of the foam layer under the thermal radiation environment of different conditions are discussed. The results indicate that the high temperature generated by the radiative heat flux will accelerate the collapse rate of the foam layer. The stability of the foam structure will be seriously damaged. There is a relationship between heat radiation intensity and foam attenuation coefficient. The empirical model for reflecting the fire‐fighting foam collapse process under the fire environment with high heat radiation flux is modified. Moreover, the average collapse rate and temperature difference gradient are used to characterize the thermal stability performance and heat insulation characteristics of the foam. Analysis of the micro‐scale foam structure parameters from the foam scans has revealed that the thermal stability performance and heat insulation characteristics of the foam are stronger when the surface tension of the foam is within the range of 17.4–20.4 mN/m.