Abstract
In order to solve the contradiction between the increasing demand of power supplies and the difficulty of building new distribution lines, improving the transmission capacity of existing distribution cables is imperative. Using emergency ampacity can increase cable transmission capacity temporarily. Software of calculation emergency ampacity of distribution cable is developed and experiments are undertaken in this paper. The consistency of calculation and experiments shows that the software could calculate emergency ampacity of distribution cable correctly. By the software, the relationship between emergency ampacity and emergency time & initial status are studied here. The research shows that emergency ampacity is much higher than the continuous ampacity. What’s more, the shorter emergency time is, the higher emergency ampacity will be. The lower initial current is, the higher emergency ampacity will be. The more cable circuit number is, the lower emergency ampacity will be but the stronger lifting capacity will be. If emergency ampacity is considered in cable line design stage, cable cross-section or the number of circuit number could be reduced; and if emergency ampacity is considered in emergency load control, the number and capacity of transferring power supply can be reduced. The application the emergency ampacity of distribution cable will result in a great improvement in economy and reliability of power supply.