Abstract
The experimental study was carried out to explore the influence of refrigerant charging amount on the performance of the heat pump system. In the experiment, the amount of refrigerant to be charged was reflected by the pressure during refrigerant charging, and the pressure during refrigerant charging was changed to be 4.5 MPa, 5MPa, 5.5 MPa, 6 MPa and 6.5MPa, the ambient temperature was 25°,C and the outlet water temperature of the heat pump was set to 65°C. Experimental research showed that the refrigerant filling quantity change would affect the CO2 air source heat pump system performance parameters, When the refrigerant charging amount increased, the system had the minimum power consumption and the maximum COP, and the system heat production increased gradually, and the time consuming decreased first and then increased. When the pressure of refrigerant was 6MPa, the CO<sub>2</sub> air source heat pump system reached the best operating condition, with the minimum power consumption of 0.79kW and the maximum COP of 5.11.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.