Abstract

In the current design method of the eccentrically braced frame structure, the energy dissipation link and the frame beam are both designed as a whole. It is difficult to accurately assess the degree of damage through this method, and it is also hard to repair or replace the energy dissipation link after strong seismic events. Meanwhile, the overall design approach will increase the project’s overall cost. In order to solve the above mentioned shortcomings, the energy dissipation link is designed as an independent component, which is separated from the frame beam. In this paper, the energy dissipation link is bolted to the web of the frame beam. Both finite element simulation and test study of eight groups of energy dissipation links have been completed to study their mechanical behaviors, and the energy dissipation links have been studied in the aspects of length, cross section, and stiffener spacing. The mechanical behaviors include the energy dissipation behavior, bearing capacity, stiffness, and plastic rotation angle. The results indicate clearly that the hysteretic loop of links in the test and finite element analysis is relatively full. By comparing the experimental and finite element simulation data, it can be found that the general shape and trend of hysteretic loop, skeleton curve, and stiffness degradation curve are basically the same. The experiment data explicitly shows that the energy dissipation link of web-connected displays good ductility and stable energy dissipation ability. In addition, the replaceable links possess good rotational capacity when the minimum rotation angle of each specimen in the test is 0.16 rad. The results of the experiment show that the energy dissipation capacity of the link is mainly related to the section size and the stiffening rib spacing of the link. The energy dissipation ability and deformation ability of the link is poorer as the section size becomes larger; meanwhile, these abilities are reduced with the decrease of the stiffening spacing. The experiment result shows that the damage and excessive inelastic deformations are concentrated in the link to avoid any issues for the rest of the surrounding elements, and the links can be easily and inexpensively replaced after strong seismic events. The results are thought provoking, as they provide a theoretical basis for the further study of the eccentrically braced frame structure with replaceable links of web-connected. In future work, the author aims to carry out his studies through optimized design methodology based on the yielding criterion.

Highlights

  • In the current practice, the energy dissipation link and frame beam are designed as a whole, which makes the replacement procedure rather difficult

  • AlessandroZona presented a hybrid coupled wall (HCW) system that was made of a single reinforced concrete (RC) wall coupled to two steel side columns by means of steel links

  • By referring to the design idea that was proposed by Nabil [46,47,48], the energy dissipation link and the frame beam of the eccentrically braced frame connected pass through the high-strength bolts

Read more

Summary

Introduction

The energy dissipation link and frame beam are designed as a whole, which makes the replacement procedure rather difficult. Since the 2000s, Dubina and Stratan [33,35,36] studied a link-to-beam connection with bolted end-plates and concluded that the link length ratio should be limited to 0.8 for the sake of preferable hysteretic behavior. The author put forward a replaceable link detail, which was based on splicing the directly connected braces and the beam outside the link The validity of this method has been verified by eight near-full-size EBF tests under quasi-static cyclic loading. Based on the results of the experimental and numerical study, the links of web-connected exhibit a very good ductile behavior, stable energy dissipation capacity, and high rotation capacities, which is easy to replace. Some useful conclusions are drawn to provide suggestions and design recommendations for the follow-up researches

Experimental Program
Specimen Design and Material Properties
Material Properties
Test Setup and Instrumentation
Test Point Layout and Data Collection
Loading Protocol
Experimental and Discussion
Failure Mode
Stress Analysis
Hysteretic Performance
11. Hysteretic
Skeleton
Stiffness Degradation
Verification of Finite Element Models
The Result Analysis of Test and Finite Element
StressFigure
17. Stress
5.5.Conclusions
Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.