Abstract
Through the combustion experiments on the cables and servers in a data room, the combustion characteristic parameters of the materials were obtained, and the materials were analyzed and evaluated from the aspects of heat release rate, gas concentration, flue gas temperature, and so on. The results show that network cable and electric cable can be ignited during the cable combustion test. In the overall fire combustion experiment of single server and the server group with three cabinets, the fire process is divided into three stages: initial growth stage, stable combustion stage, and combustion attenuation stage. The heat release rate, flue gas temperature, and CO2 concentration of the overall experiment have three peaks, respectively, 58, 98, and 134 kW; 100°C, 152°C, and 232°C; 1314, 2514, and 2988 ppm. The research results can provide some reference for design of fire protection system in data rooms.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.