Abstract

The high operating pressure of a twin-screw compressor employed in high temperature heat pump or NH3/CO2 cascade refrigeration systems often leads to extremely large axial force on the compressor rotors. Accurate calculation of this axial force is very important in selection of bearing and design of balancing pistons. In this paper, an experimental study of the axial force on the twin-screw compressor rotors was conducted. The variations of the axial force under different operating conditions were investigated. Furthermore, the axial force was also calculated by employing the mean pressure model and sector pressure model, and was compared with that of the experimental results. It was concluded that the sector pressure model is more accurate in predicting the axial force on the rotors in comparison with that of the mean pressure model. However, the mean pressure model was more accurate under operating conditions with large built-in volume ratio. Moreover, the axial force on the rotor end face was found to have larger influence than that on the rotor helical surface.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.