Abstract
Effect of water mist on the small-scale solid fuel PVC (poly vinyl chloride) fire in a confined space has been studied experimentally using a cone calorimeter. In this study, the combustion characteristics of PVC, and the interaction between the water mists and the diffusion flame in a confined space with proper ventilation control are studied under various conditions in the cone calorimeter. The water mist is generated by a single pressure nozzle and the diffusion flame is produced from PVC samples, respectively. The Laser Doppler Velocimetry/Adaptive Phase Doppler Velocimetry LDV/APV system is employed to determine the water mist characteristics. The results of the test showed that the combustion of PVC is a two-step process, the water mist suppress the diffusion flame in a confined space via oxygen displacement, heat extraction, and heat radiant attenuation. Heat extraction (flame cooling and fuel surface cooling) plays a dominant role by suppressing the PVC fire when the water mists of enough volume flux are applied to the diffusion flame in a confined space. The higher the operational pressure, the easier the suppression.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.