Abstract
The article presents an experimental study of high breaking capacity fuses with aluminum fusible element with and without a eutectic point, at minimum rated breaking current, preceded by experiments at maximum rated breaking current. The paper shows that in the construction with aluminum fusible element, the fuse has no problem breaking the maximum rated breaking current, but real difficulties appears when it comes to the minimum rated breaking current. The experiments were made on a homogeneous series 6-20 A, with a focus on the 36 kV, 25 kA, 16 A fuse. The fuses suffered multiple construction changes and tests with and without a eutectic point. After several tests was found an acceptable constructive solution was, but the obtained value for the minimum rated breaking current is not a commercially attractive value. It was also tested the capacity of the fuse to transfer the breaking duty to a load break switch.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
More From: Annals of the University of Craiova, Electrical Engineering Series
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.