Abstract
This study presents evaporative heat transfer characteristics of CO 2/propane refrigerant mixtures in horizontal, and vertical smooth and micro-fin tubes. The effect of mass flux, heat flux, inlet temperature and several compositions have been investigated and analyzed. The copper tube with outer diameter of 5 mm and length of 1.44 m was selected as the test sections. Average inner diameters of test tubes are 4.0 mm and 4.13 mm, respectively. The tests were conducted at mass fluxes from 212 to 656 kg/m 2, heat fluxes from 15 to 60 kW/m 2, inlet temperatures from −10 to 30 °C, and for several compositions (75/25, 50/50, 25/75 wt%). Among CO 2/propane refrigerant mixtures, the heat transfer characteristics are much better than those of any other compositions when the composition is 75/25 (wt%). Finally, the heat transfer coefficients of CO 2/propane refrigerant mixtures in the vertical tube are 5–10% higher than those in horizontal tubes.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.