Abstract
A technique to discriminate between the line charging inrush current and the current resulting on closing or auto-reclosing a faulted EHV/UHV transmission line has been implemented on a 32-bit digital signal processor (DSP) board. The technique is based on the voltage signals before switching and the current signals. This technique is proposed to be a supplement to the main protection schemes for both single-circuit and double-circuit lines. The scheme is tested on a physical model of a transmission system with a source at each end. Laboratory tests show that the proposed technique is effective for three-pole and single-pole reclosing on a faulted or healthy line.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.