Abstract

In this paper, the performance of an ejector cooling system with constant-area mixing chamber was investigated at low generator temperatures. The cooling system was tested by using hot water as driving fluid and R123 as working fluid. The effects of operating temperatures on the cooling capacity and on the coefficient of performance (COP) of the system were experimentally investigated at an ejector area ratio of 7.17, which is suitable for solar cooling. As a result, COP of 0.42 was obtained at a vapor generator temperature of 74°C, evaporator temperature of 10°C, and at a critical condenser temperature of 29°C. A solar application of the system with single-glazed selective-type collectors in a horizontal position was conducted as a preliminary study. In the solar application, a cooling capacity of 1080 W for a 9.2 m2 collection area at an evaporator temperature of 10°C was obtained.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.