Abstract

This paper presents an experimental study about the effect of condenser subcooling on the performance of an air conditioning system operating with R134a and R1234yf, under the same operating conditions. For both refrigerants, it has been shown that the COP undergoes a maximum as a consequence of the trade-off between increasing refrigerating effect and increasing specific compression work. At a given operating condition, the system COP increased up to 18% for R1234yf and 9% for R134a. These results confirmed the trends obtained from a previous theoretical analysis, demonstrating that a system operating with R1234yf can benefit more from the condenser subcooling than that with R134a. The experimental results also showed that the presence of an internal heat exchanger significantly reduces the COP increase due to condenser subcooling, since both improvements compete towards reducing the throttling losses. Besides the interference between IHX and condenser subcooling, the use of both simultaneously still yields a more efficient air conditioning system, especially for R1234yf.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.