Abstract

This paper presents a theoretical study about the effect of condenser subcooling on the performance of vapor-compression systems. It is shown that, as condenser subcooling increases, the COP reaches a maximum as a result of a trade-off between increasing refrigerating effect and specific compression work. The thermodynamic properties associated with the relative increase in refrigerating effect, i.e. liquid specific heat and latent heat of vaporization, are dominant to determine the maximum COP improvement with condenser subcooling. Refrigerants with large latent heat of vaporization tend to benefit less from condenser subcooling. For an air conditioning system, results indicate that the R1234yf (+8.4%) would benefit the most from condenser subcooling in comparison to R410A (7.0%), R134a (5.9%) and R717 (2.7%) due to its smaller latent heat of vaporization. On the other hand, the value of COP maximizing subcooling does not seem to be a strong function of thermodynamic properties.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.