In the area of buildings refrigeration, the use of thermal energy storages coupled with heat pumps is a significant way for reducing the operating costs and optimizing the design of equipment. In this paper, a prototype of large-scale refrigeration - PCM (Phase Change Material) energy storage system is described, from which experimental results on transient behavior are obtained. A dynamic model for transient simulation of the coupled system is presented. The fluid flows through the heat exchangers and the storage tank are represented by a cascade of Continuous Stirred Tank Reactors (CSTRs). Switching procedures between different model configurations associated to phase transitions within heat exchangers and PCM storage tank are mathematically performed by matrix operations. The compressor, the expansion valve and the pressure drop across the evaporator are represented by static models based on empirical correlations. A PI controller for the expansion valve opening is integrated in the heat pump model to maintain the superheat at evaporator exit. The model is validated by a complete and detailed comparison between simulation and experimental results.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.