Abstract

The steam condensation process has been experimentally investigated in an air-cooled condenser (ACC). The ACC has been designed and built using a flattened cross-section horizontal tube. The flattened tube has an internal dimension of 102 mm x 12 mm with 4030 mm length. A range of vacuum operating conditions are applied to operate the ACC. In the experiments, parameters such as vacuum pressure, saturated temperature, wall tube temperature, rate of heat transfer, and local average steam heat transfer coefficient have been considered along the flow direction with the variation of cooling water temperature. The experimental results revealed that the steam saturated temperature and the related pressure decrease with the reduction of the cooling water temperature, and the temperatures of the upper and lower parts of the horizontal flattened tube. The results also showed that the local steam condensation heat transfer coefficient decreases along with the direction of the flow, but it there is incrementing with the decreasing of saturated steam temperature at a certain range of cooling water temperature.