Abstract
To experimentally evaluate the performance of an ejector working as a liquid re-circulator in a horizontal-tube falling-film evaporator with R134a, experimental tests are performed using a horizontal-tube falling-film water chiller prototype. Experimental observations on intertube liquid flow pattern of tube bundle validate the feasibility of the liquid re-circulation system using a liquid–liquid ejector. The analysis results show that the influence of the motive flow rate on the entrainment ratio of the ejector is small, and the average entrainment ratio of the ejector is about 2.03. With the increase of the valve opening of the regulating valve, the evaporating capacity of the falling-film water chiller rises 4.8%, from 940.2 kW with the re-circulation ratio of one, to 985.5 kW with the re-circulation ratio of 1.135. The COP of the falling-film water chiller reaches a maximum and then drops down with the increase of the re-circulation ratio, and the optimal re-circulation ratio is 1.135.