Abstract
The proximity of obstacles in a ventilation network can result in a significant increase of the noise production. In this paper, a tandem diaphragm inserted in a rigid duct with rectangular cross section is investigated and compared to a single diaphragm obstruction. The disturbed flow which reaches the second obstacle causes an amplification of the radiated noise which goes beyond a simple doubling of the power. Experimental results, carried with various spacing between the two diaphragms and bulk velocity, allows identifying other aeroacoustic source mechanisms which does not appear with a single diaphragm. Depending on the configuration, the broadband level can increase by more than 10 dB and feedback phenomena can appear at low frequency. Explanations and illustrations of those phenomena are given thanks to compressible-fluid simulations.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.