Abstract

The performance of CO 2 ejector refrigeration system needs further improvement to make CO 2 more viable than traditional harmful refrigerants. In this research, the effect of internal heat exchanger (IHX) in the performance of ejector refrigeration system was analyzed experimentally and compared with conventional expansion refrigeration system. Experiments were performed at different operating pressure and temperature for the cases of without IHX, 30 cm IHX and 60 cm IHX. The results showed that IHX significantly increased the coefficient of performance (COP) of ejector system. At the conditions used in this research, the ejector system with 60 cm IHX provided the maximum COP improvement of up to 27% compared to similar conventional system. The motive nozzle’s inlet condition had significant effect on the performance of ejector system. The results also confirmed the presence of considerable amount of liquid refrigerant at separator’s gas outlet of ejector system which was deemed possible in our previous research.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.