Abstract

This study aims to determine the performance improvement of a vapor compression systems that use expansion parallel liquid refrigerant. The experiment was conducted by replacing the single expansion device with a parallel expansion device on a vapor compression systems. The working fluid is used as a cooling medium is R-290. To get performance data, measurements performed on the cooling load with various temperatures (range from 3C to - 3C). Finally, The results showed that expansion parallel liquid refrigerant on a vapor compression systems generates an increase in refrigerating efect and COP of 49% and 2,5%, respectively. This has implication to saving the power consumption of the vapor compression systems.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.