Abstract
Abstract To improve the sensitive and reliability of condition monitoring in gas insulated switchgear (GIS), discharge perception system applied to GIS insulators protrusion discharge based on single ultraviolet photon is built. Step method is used to inspire the discharges of different severity, based on which, the regression relationship of ultraviolet (UV) signal and electrical signal are studied, and the perception mechanism of UV signal in different severity of discharges is analyzed. The study indicates that, the development of protrusion discharge in GIS can be divided into four stages, and there is no positive correlation between the number of ultraviolet photons caused by discharge radiation and insulation deterioration level, but related to the diffusion, migration and recombination of charged particles, then UV optical method for quantitative monitoring of discharge in each stage is provided, which provide a new method for quantitative measurement of GIS insulator discharge.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.