Abstract

UHF electromagnetic wave has been widely used in various PD measurements of GIS (gas insulated switchgear) because of its high sensitivity, strong anti-interference ability, large effective detection range, fault location and pattern recognition. In this paper, a new method of detecting partial discharge of pouring hole on GIS insulator is studied. The transmission characteristics of UHF electromagnetic wave are simulated by FDTD. Based on the computer simulation technology (CST), a dipole antenna UHF sensor is developed. Finally, the sensitivity and validity of the sensor are tested on the 110kvgis experimental platform. Compared with the conventional method, the sensitivity of PD detection in GIS is obviously improved.